17KV zno lightning arrester without gap
material: ZnO varistor, silicon rubber housing
certification:ISO9001
package: Carton
confirm to IEC60099-4, IEC37-199/CDV
Technicial Parameter
MOA Type | Sys R.V | MOA R.V | MCOV | D.C.U1mA | 1/10μs steep current impulse | 8/20μs lightning current impulse | 30/60μs Switching current impulse | 2ms rectangular current impulse withstand | 4/10μs high current impulse withstand | ||
KV(r.m.s) | ≥KV | ≤KV | A | KA | |||||||
HY5WS-3.8/15 | 3 | 3.8 | 2.0 | 7.5 | 17.3 | 15 | 12.8 | 75 | 40 | ||
HY5WS-5/15 | 5 | 4.0 | 8.0 | 17.3 | 15 | 12.8 | 90 | 65 | |||
HY5WS-7.6/30 | 6 | 7.6 | 4.0 | 15.0 | 34.5 | 30 | 25.5 | 75 | 40 | ||
HY5WS-10/30 | 10 | 8.0 | 15.0 | 34.5 | 30 | 25.5 | 90 | 65 | |||
HY5WS-12.7/50 | 10 | 12.7 | 6.6 | 25.0 | 57.5 | 50.0 | 38.5 | 75 | 40 | ||
HY5WS-17/50 | 17 | 13.6 | 25.0 | 57.5 | 50.0 | 38.5 | 90 | 65 |
Normal service conditions:
The ambient air temperature is no higher than +40 degree. no lower than -40 degree.
The altitude above sea level does not exceed 2000m
Power frequency 48Hz~62Hz
Maximum wind speed does not exceed 35m/s
The earthquake intensity does not exceed 7 degrees
The voltage that long-time exerted shouldn't exceed its Max MCOV